Eaton 9395XMegawatt UPS with silicon carbide

Eaton's new UPS for data centres and critical infrastructure delivers 900–1,700 kW in a single system. Silicon carbide (SiC) power electronics give up to 97.5 % efficiency in double conversion, and according to Eaton the system takes up to 30 % less floor space.

Eaton 9395X UPS system
Eaton product photo
900–1,700 kWPower at power factor 1.0
97,5 %Double-conversion efficiency
99,1 %Efficiency in ESS mode
300–375 kWPer power module, up to five per system

The technology

More power on less floor

The 9395X is Eaton's first large UPS with silicon carbide power semiconductors. SiC components switch faster and with lower losses than traditional silicon IGBTs. The difference can be measured directly in a data centre: less space for the UPS, less heat to remove and more power per square metre.

Air is drawn in at the front and exhausted at the top. No clearance is therefore needed behind the system, and it can stand against a wall or back to back with another system.

Floor plan of Eaton 9395X 1,700 kW: 3.22 × 0.92 m with I/O section and five power modules I/O 340 kW340 kW340 kW340 kW340 kW 3.22 m 0.92 m FOOTPRINT 2.96 m² POWER PER M² approx. 574 kW
Eaton 9395X 1,700 kW seen from above: I/O section and five 340 kW power modules. Dimensions for single feed according to Eaton's technical specification.

Up to 30 % less floor space

Every square metre in a data centre is planned for IT. A smaller UPS room frees up space for racks.

Up to 50 % higher power density

1,700 kW stands on 3.22 × 0.92 m. That is approx. 574 kW per square metre of footprint.

Up to 30 % lower heat loss

Lower heat loss means less cooling to size, pay for and maintain.

The percentages are Eaton's own and compare with earlier generations of the 9395.

Energy use

Highest efficiency at part load

A UPS in a data centre rarely runs at full load. With 2N redundancy each system is loaded to 50 % at most, and with N+1 the load is also below full load. It is precisely between 25 and 50 % load that the 9395X reaches its highest double-conversion efficiency: 97.5 %.

ESS mode

In ESS mode (Energy Saver System) the load is supplied via bypass while the system monitors the mains. On a mains fault it switches to double conversion in under 2 ms, so the IT equipment does not notice the transfer. Efficiency is 99.0–99.1 % at 25–100 % load.

Efficiency of Eaton 9395X at 25, 50, 75 and 100 % load 99 %98 %97 %96 %95 % 25 %50 %75 %100 % 97,5 % 96,1 % ESS mode Double conversion
Eaton 9395X 1,700 kW at 400 V according to Eaton's technical specification.
Double-conversion efficiency and heat loss, 400 V
Model25 % load50 % load75 % load100 % loadHeat loss at 100 %
900 kW97,5 %97,5 %97,1 %96,5 %32.6 kW
1,020 kW97,4 %97,5 %97,0 %96,1 %41.4 kW
1,125 kW97,5 %97,5 %96,9 %96,1 %45.7 kW
1,500 kW97,5 %97,5 %97,1 %96,5 %54.4 kW
1,700 kW97,4 %97,5 %97,0 %96,1 %69.0 kW

Design

Power modules that configure themselves

The system is built from 300, 340 or 375 kW power modules (UPMs) in a common frame with I/O section and static bypass. The modules are plug-in and configure themselves when inserted. Up to four systems can be paralleled with Eaton's HotSync.

How we size

We always size with 25 % room for expansion. In the 9395X that means a frame with free module slots, not modules running unloaded from day one. Cables, fuses and switchboards are sized for the frame's full rating, so expansion does not require rebuilding the installation.

Eaton 9395X frame seen from the front with four power modules and one free module slot I/O bypass 340 kW340 kW340 kW340 kW Free slot In operation: 4 × 340 kW = 1,360 kW Frame: 1,700 kW
Example: a 1,700 kW frame with four power modules and one free slot for expansion.

1–5 modules per system

Power follows the number of modules, up to the frame size.

Up to four systems in parallel

HotSync shares the load between systems without a communication link for synchronisation and load sharing.

Service without dropping the load

A module can be removed for service while the other modules supply the load.

Models

Seven power ratings from 900 to 1,700 kW

The model designation states the system's rating. Dimensions apply to single feed (small I/O section). With separate bypass feed (large I/O section) the system is 400 mm wider and 140 kg heavier. The price depends on configuration, batteries and installation, so we quote after sizing.

ModelPowerPower modulesW × D × HWeight, fully equipped
9395XP-900900 kW3 × 300 kW2,495 × 920 × 2,070 mm2,540 kg
9395XP-10201,020 kW3 × 340 kW2,495 × 920 × 2,070 mm2,540 kg
9395XP-11251,125 kW3 × 375 kW2,495 × 920 × 2,070 mm2,540 kg
9395XP-12001,200 kW4 × 300 kW2,830 × 920 × 2,070 mm2,900 kg
9395XP-13601,360 kW4 × 340 kW2,830 × 920 × 2,070 mm2,900 kg
9395XP-15001,500 kW5 × 300 kW3,220 × 920 × 2,070 mm3,450 kg
9395XP-17001,700 kW5 × 340 kW3,220 × 920 × 2,070 mm3,450 kg

Batteries

VRLA today, lithium-ion when you are ready

The 9395X works with a DC voltage window of up to 700 V and can be supplied from VRLA, lithium-ion and NiCd batteries. The batteries are charged with Eaton's ABM technology, which charges in periods and rests in between instead of holding the batteries at constant voltage. This is gentler on the batteries.

Our standard fits directly

We build battery systems with CSB blocks to Eurobat 10+ years, 40 blocks per string and at least two strings on Kunstmann racks. 40 blocks are within the voltage window of the 1,020 and 1,700 kW models, and we set the end-of-discharge voltage to 1.75 V per cell ourselves, within Eaton's range of 1.67–1.75 V.

Two battery strings of 40 blocks each, connected to the UPS DC input · · ·· · · STRING 1 · 40 BLOCKSSTRING 2 · 40 BLOCKS 9395X DC input 40 × 12 V = 480 V nominal Within 400–700 V DC on 1,020 and 1,700 kW
Two parallel strings give redundancy in the battery system: a defective block does not take the whole backup with it.
VRLA batteries per string
ModelBlocksCellsDC voltage
900 and 1,500 kW36–50216–300360–700 V
1,020 and 1,700 kW40–50240–300400–700 V
1,125 kW44–50258–300440–700 V
Lithium-ion compared with VRLA, according to Eaton
Space50–80 % less
Weight60–70 % lower
Recharging2–3 times faster
Service lifeUp to 2 times longer

Operation and security

Built for operations that must not stop

A system of this size often protects an entire data centre. That is why much of the 9395X is about detecting faults early, keeping the load supplied during service and being able to document that the system works.

Two parallel 9395X systems with HotSync share the load without a communication link 9395X · A 9395X · B HotSync HotSync No control link Critical load
Each system regulates its own share of the load based on voltage and frequency. A fault in a control link can therefore not take both systems down.

HotSync without a single point of failure

Parallel systems share the load without a communication link for synchronisation and load sharing.

Fault discrimination

The system distinguishes between faults upstream and downstream of the UPS and reacts so that the critical load is protected.

Easy Capacity Test

The UPS can be tested at full load without an external load bank, because the energy is circulated internally. During commissioning we still test batteries, generator, cables and cooling with a load bank.

Cybersecurity

The network cards are certified to IEC 62443-4-2 and UL 2900-1. Eaton Cyber Secured Monitoring provides monitoring and health reports via a secured cloud.

EnergyAware

With lithium-ion batteries, part of the battery capacity can be made available to the grid. Eaton states typically up to €50,000 a year per MW allocated to grid support.

Technical data

Eaton 9395X in figures

Data for the 400 V version according to Eaton's technical specifications. Where values depend on the model, the range for the whole series is shown.

TopologyOnline double conversion, transformerless with SiC
Power900–1,700 kW at power factor 1.0
Power modules1–5 modules of 300, 340 or 375 kW
ParallelingUp to 4 systems with HotSync
Input voltage400 V, 3-phase, 50 or 60 Hz
Input, current distortionTHDi below 3 %, input power factor 0.99 above 60 % load
Output voltage220/380, 230/400 or 240/415 V, 3 phases + N + PE
Output, regulation±1 %, THDu below 1 % with linear load and below 5 % with non-linear load
Overload, inverter (1,700 kW)110 % for 10 min, 125 % for 60 s, 150 % for 10 s
BypassStatic, no-break transfer, below 115 % continuously
Short-circuit ratingIcc 100 kA on AC input and bypass, Icw 100 kA for 10 ms on DC input
EfficiencyUp to 97.5 % in double conversion, 99.0–99.1 % in ESS mode
BatteriesVRLA, lithium-ion and NiCd, up to 700 V DC, end-of-discharge voltage 1.67–1.75 V per cell
Charging currentDefault 120 A per power module, adjustable
Noise at 1 mBelow 83–85 dB(A) at 100 % load, below 62–70 dB(A) at 50 % load
Cable entryAC at the top, DC at the top or bottom
CoolingAir in at the front and out at the top, no clearance behind the system
Environment0–40 °C (recommended 20–25 °C), up to 1,000 m without derating, 2,000 m with 1 % derating per 100 m
Degree of protectionIP20
CommunicationColour touchscreen, Modbus TCP, BACnet/IP and SNMP v1/v3 via network card, 5 galvanically isolated alarm inputs
StandardsIEC 62040-1, IEC 62040-2 (C3), IEC 62040-3, IEC 62443-4-2 and UL 2900-1, RoHS and WEEE

Sources: Eaton 9395X brochure BR153158EN (February 2024), datasheet PS153066EN (March 2024) and technical specifications for 9395XP 900–1,020 kW (rev. 003), 1,125 kW (rev. 001) and 1,500–1,700 kW (rev. 010), all April 2025.

Bluecircle

From sizing to operation

We size the 9395X to your preparedness plan, deliver and commission the system and service it afterwards with a guaranteed response time.

Should the 9395X be sized for your data centre?

Send us the load in kW, the required autonomy time and the redundancy level. We will get back to you with a sizing and a quotation.

+45 7012 1317kontakt@blue-circle.dkGet a quotation