Battery room with UPS batteries on battery racks

UPS batteries

Battery rack, battery cabinet or internal batteries?

Internal batteries when the autonomy can be reached with the space in the UPS cabinet. A battery cabinet when the batteries must stand by the UPS system in a room other people also use. A battery rack when the battery bank is large and can stand in a locked battery room.

Quick answer

Three locations. Three different needs.

Where a UPS system's batteries should go depends on three things: the autonomy required by the contingency plan, the space by the UPS system and who has access to the room.

The table shows the differences. Not sure what your system needs? Enter your load and required autonomy in the UPS selector and get a price for the complete system.

InternalCabinetRack
The same battery blocks, three locations: inside the UPS cabinet, in a closed cabinet next to it or on racks in a locked battery room.
Internal batteriesBattery cabinetBattery rack
LocationInside the UPS cabinetClosed steel cabinet next to the UPS systemOpen frame in a separate battery room
Best forAutonomy that can be reached with the blocks in the UPS cabinetRooms that other people also useLong autonomy and large battery blocks
Floor spaceNone extraOne or more cabinets by the UPS systemMost, including the aisle in front of the racks
AccessBehind the UPS doorsClosed, locked cabinetLocked room for instructed personnel only
ExpansionFree battery slots in the cabinet onlyMore cabinetsMore or longer racks

How to choose

Start with the autonomy, not with the cabinet

The location follows from the battery bank the system needs. That is why we always work in the same order.

  1. 01

    Autonomy from the contingency plan. The contingency plan sets how long the UPS system must carry the load – for example until the generator has taken over or the equipment has been shut down in a controlled way.

  2. 02

    The battery bank. Load and autonomy give the number of strings and the block size. If they fit in the UPS cabinet, internal batteries are the simplest option.

  3. 03

    The room. If the batteries must stand by the UPS system where other people also work, it becomes a locked battery cabinet. If the bank is large or the blocks are heavy, it becomes racks in a locked battery room.

Business continuity plan
  1. 01Internal batteriesThe autonomy can be reached with the blocks in the UPS cabinet
  2. 02Battery cabinetThe batteries must stand by the UPS system, and other people use the room
  3. 03Battery rackLarge battery bank or heavy blocks in a locked battery room

Internal batteries

Batteries in the UPS cabinet

Many UPS systems come in a version with battery slots in the same cabinet as the modules. It is the most compact solution, but the autonomy is limited by the number of slots.

  • No extra floor space and no battery cables between cabinets.
  • The autonomy depends on the load: the same batteries give far less time at full load than at low load.
  • Service and replacement of the blocks take place inside the UPS system.
  • If longer time is required, a battery cabinet can be connected.
Internal battery blocks on battery trays in a UPS cabinet

Backup time at 20 kW, internal batteries

  1. CAB-SP060-I080strings × blocks × Ah: 2 × 40 × 9 Ah10 min
  2. CAB-SP060-I240strings × blocks × Ah: 3 × 40 × 9 Ah19 min
  3. CAB-SP120-I320strings × blocks × Ah: 1 × 40 × 28 Ah22 min
  4. CAB-SP120-I320strings × blocks × Ah: 2 × 40 × 28 Ah55 min
Data from Centiel StratusPower 400V Technical Specifications, REV08. At higher load the time is shorter.
Centiel StratusPower

CAB-SP060-I080-2S-A1

Centiel StratusPower CAB-SP060-I080-2S-A1
Internal batteries
80 × 9 Ah
Max. power
60 kW
See in the shop
Centiel StratusPower

CAB-SP060-I240-2S-A0

Centiel StratusPower CAB-SP060-I240-2S-A0
Internal batteries
240 × 9 Ah
Max. power
60 kW
See in the shop
Centiel StratusPower

CAB-SP120-I320-4S-B0

Centiel StratusPower CAB-SP120-I320-4S-B0
Internal batteries
320 × 9 Ah or 80 × 28 Ah
Max. power
120 kW
See in the shop

Rack or cabinet

External batteries: battery cabinet or battery rack

If the batteries are to stand outside the UPS system, the choice is between a closed battery cabinet and an open battery rack. Both carry the same battery blocks. The difference is how the blocks are protected, how many there is room for and where they may stand.

Battery cabinetBattery rack
ConstructionClosed steel cabinet with doors and lockOpen frame on several tiers
LocationNext to the UPS system, also in rooms other people useIn a locked battery room
ProtectionThe cabinet protects against contactThe room and its lock protect against contact
CapacityFixed number of blocks per cabinetBuilt to the block and the length of the room
Large blocksLimited by the cabinet's dimensionsAlso large and heavy blocks
InstallationDelivered as a cabinet and tilted into placeAssembled in the room
ExpansionOne more cabinetA longer rack or one more rack
operating areaaisleCabinetBattery room
The cabinet is the protection itself and can stand by the UPS system. The rack is open, so the locked room is the protection.
Battery rack with UPS batteries behind transparent touch guards
01

Battery cabinets

ZincFive BC 2 battery cabinets, one with the door open

Closed, lockable steel cabinets that stand right next to the UPS system – even in rooms other people use. We have pre-calculated almost 1,900 cabinet sizes for 158 battery types from 1 to 12 strings, and if no standard cabinet fits, we build it to measure. Complete nickel-zinc and lithium systems too.

Price
From €870 per cabinet, excl. VAT, delivery and installation
Battery types
158 pre-calculated
Strings
1–12 per solution – and more cabinets side by side
Height
900–2,200 mm
See battery cabinets in the shop
02

Battery racks

Battery rack with UPS batteries on three tiers

Steel racks built for the chosen block and the room’s dimensions – on one or several tiers and up to 15 m in one rack. More than 9,700 pre-calculated variants for 157 battery types from 1 to 12 strings, including the largest and heaviest blocks.

Price
From €468 per rack, excl. VAT, delivery and installation
Battery types
157 pre-calculated
Strings
1–12 per solution – and more racks as the bank grows
Length
Up to 15 m in one rack
See battery racks in the shop

Room and safety

The requirements of EN IEC 62485-2

EN IEC 62485-2 is the European standard for the safety of stationary batteries. It applies to both cabinets and racks and determines where the batteries may stand and how much air the room must have.

Locked battery room with battery racks, battery switchboards and ventilation grille
RequirementWhat it means
Restricted access above 120 V DCBatteries above 120 V DC must be located with restricted access, secured by a lock. A string of 40 blocks of 12 V is at about 480 V DC.
Touch voltageA nominal touch voltage of 120 V DC must not be exceeded.
VentilationThe airflow is calculated as Q = 0.05 × n × Igas × Crt × 10⁻³ m³/h. Three strings of 40 blocks of 100 Ah (720 cells) on float charge of VRLA give about 3.6 m³/h.
Maintenance in sectionsBatteries above 120 V DC should be divisible into sections of no more than 120 V DC when work is carried out on them.
Working distancesThe standard sets working distances in battery rooms, so the racks must be planned with space in front of the blocks.
Lithium-ionIEC 62485-5 applies to stationary lithium-ion batteries.

The floor and the temperature

Batteries are heavy. Under the Danish national annex to Eurocode 1, an office floor is designed for an imposed load of 2.5 kN/m², while the load under a full battery cabinet can be more than ten times higher. We state the calculated floor load for the chosen solution so an engineer can assess the floor before the system is installed.

Battery design life is stated per Eurobat at 20 °C and halves for every 10 °C the temperature is constantly above that. The room must therefore be kept cool – whether the batteries are in a cabinet or on racks.

Temperature and service life

Floor load

  1. Office floor, imposed load per DS/EN 1991-1-1 DK NAapprox. 255 kg/m²
  2. Under a full battery cabinet, exampleapprox. 2,800 kg/m²
The office floor is designed for 2.5 kN/m². The example is the manufacturer's calculated floor load under one of our standard cabinets.

Our sizing

How we build the battery bank

Whatever the location, we size the batteries on the same principles, so the system can be serviced and expanded without compromising the autonomy.

  1. 01Blocks in the Eurobat 10–12 year classCSB blocks with design life per Eurobat at 20 °C
  2. 0240 blocks per string, at least 2 and preferably 3 stringsOne string can be taken out for service while the others provide battery time
  3. 03End-of-discharge voltage 1.75 V per cellWe set the UPS system ourselves so the blocks are not deep-discharged
  4. 04Four cables per stringStrings in Centiel systems have a midpoint (N), so each string is run with +, − and N from both halves to the battery switchboard
  5. 05Installation for full capacityCables, fuses and switchboards are sized for the system's full capacity with 25 % expansion
UPSBattery switchboard
Three strings with a midpoint (N): four cables per string to the battery switchboard.
Numbered VRLA blocks in a string on a battery rack

FAQ

Frequently asked questions about battery racks and battery cabinets

What is the difference between a battery rack and a battery cabinet?

A battery cabinet is a closed steel cabinet with doors and a lock that can stand next to the UPS system, also in rooms other people use. A battery rack is an open frame where the battery blocks are freely accessible, so the rack must stand in a locked battery room. The cabinet suits small and medium battery banks; the rack suits large banks and heavy blocks.

When are internal batteries enough?

When the required autonomy can be reached with the blocks that fit inside the UPS cabinet. A Centiel StratusPower cabinet with room for 80 blocks of 28 Ah gives, for example, about 55 minutes at 20 kW, but considerably less at full load. If the contingency plan requires longer, a battery cabinet or battery rack is connected.

Do UPS batteries have to be in a separate battery room?

Not always. EN IEC 62485-2 requires batteries with a nominal voltage above 120 V DC to be located with restricted access, secured by a lock. A UPS system with 40 blocks of 12 V per string is at about 480 V DC. The batteries must therefore be either in a locked cabinet or on racks in a locked battery room.

How much ventilation do UPS batteries need?

EN IEC 62485-2 calculates the required airflow as Q = 0.05 × n × Igas × Crt × 10⁻³ m³/h, where n is the number of cells, Igas is the gas-producing current per Ah and Crt is the capacity in Ah. Three strings of 40 blocks of 100 Ah (720 cells) on float charge of VRLA batteries give about 3.6 m³/h. On boost charge the gas current is higher.

Can the floor carry the batteries?

It has to be assessed case by case. Under the Danish national annex to Eurocode 1, an office floor is designed for an imposed load of 2.5 kN/m² (about 255 kg/m²). Under a full battery cabinet the load can be more than ten times higher. We state the calculated floor load for the chosen solution so an engineer can assess the floor.

How many battery strings should a UPS system have?

We design with at least 2 and preferably 3 strings of 40 blocks. One string can then be taken out for service or replacement while the others still give the system battery time.

Can the batteries be expanded later?

With battery cabinets and battery racks: yes, with more cabinets or a longer rack. Internal batteries can only be expanded as long as there are free battery slots in the UPS cabinet. We size cables, fuses and switchboards for the system's full capacity, so an expansion does not require rebuilding the installation.

The UPS selector

Get the price of the complete system – batteries included.

Enter your load and required autonomy in the UPS selector. We size the batteries and choose internal batteries, cabinet or rack to suit your room.