Samsung SDI · Lithium-ion

Samsung SDI UPS rack34.6 kWh lithium-ion battery system

A complete battery rack for UPS systems: 17 modules with Samsung SDI cells, a breaker unit with battery management and a power supply in one cabinet. The rack measures 650 × 530 mm, weighs 510 kg and can be connected in parallel with more racks when the system needs more power or longer backup time.

Samsung SDI UPS rack 34.6 kWh
Product photo of the Samsung SDI rack
34.6 kWhEnergy per rack
516.8 VNominal voltage
470 ADischarge current for 60 s
510 kgWeight with batteries

Design

Breaker, management and 17 modules in one cabinet

At the top is the breaker unit with a moulded case circuit breaker, a shunt for current measurement and the rack BMS. Below it is the power supply, which provides 24 V to the battery management and communicates with the UPS system and any parallel racks.

The modules sit in two columns. Each module has 8 cells in series and its own BMS, and the cables enter at the top of the cabinet.

The Samsung SDI rack seen from the front: breaker unit with rack BMS, power supply and 17 battery modules in two columns Breaker unitPower supply17 battery modules Breaker and rack BMS24 V for BMS8 cells per moduleOwn BMS in each 650 × 530 mm 2,055 mm high
The Samsung SDI rack seen from the front, according to the product specification.

Battery management

Every cell is monitored, all the way to the UPS system

The module BMS measures voltage and temperature and balances the cells. The rack BMS collects data from all modules and calculates the state of charge (SoC) and state of health (SoH), which the UPS system can read via RS485 or TCP/IP.

Each cell also has a safety vent, a separator that stops overcharging, a short-circuit fuse and an overcharge cut-off.

How we size

The backup time follows your emergency preparedness plan, not the battery's datasheet. We start from how long the UPS system must bridge until the generator has taken over, and build 25 % expansion capacity into the number of racks.

Battery management at three levels: cells and module BMS, rack BMS in the breaker unit and communication to the UPS system Module8 cells Rack10–17 modules UPS systemsRS485, TCP/IP Module BMSVoltageTemperatureBalancing Rack BMSState of charge (SoC)Health (SoH)Breaker UPSAlarmsDry contactParallel racks Up to 5 MW
Battery management in the rack and parallel connection of several racks.

Parallel racks

Several racks side by side

The rack is 650 mm wide and stands side by side with more racks of the same kind. The power supply in each rack communicates with the other racks and with the UPS system, so the system is managed as a whole. According to the supplier, racks can be connected in parallel up to 5 MW.

The rack must stand in a room at 18–28 °C, so we review cooling and placement before we size.

Three Samsung SDI UPS racks in parallel
Three Samsung SDI racks in parallel

Samsung SDI

Two lithium-ion solutions for UPS systems

Samsung SDI has supplied batteries for data centres since 2017. U8A3-UPS is the new high-power solution for AI data centres, while the 34.6 kWh rack is the established solution for UPS systems today.

SolutionCellsDesignSafetyStatus
SDI U8A3-UPSLMO, prismatic cellsHigh power for AI data centresFirst UPS solution to meet all criteria in UL Solutions' LSFTNew, CES 2027
UPS rack 34.6 kWhNMC/LMO, 67 Ah17 modules, 516.8 VBMS at cell, module and rack levelAvailable today

Technical data

Samsung SDI UPS rack 34.6 kWh in figures

Data from Samsung SDI's product specification and the UPS supplier's datasheet for the rack.

ChemistryLithium-ion (NMC/LMO), cells of 3.8 V and 67 Ah
Design1 breaker unit, 1 power supply and 17 battery modules with 8 cells in series each
Energy34.6 kWh
Nominal voltage516.8 V DC
Float voltage571.2 V DC
Discharge voltageRecommended end voltage 435.2 V, cut-off at 408 V
Standard charging current22.3 A (1/3 C)
Discharge current470 A for 60 seconds, 600 A for 1 second
Dimensions (W × D × H)650 × 530 × 2,055 mm
Weight510 kg with batteries, 17 kg per module
Cable connection2 conductors, cables enter at the top, cable rated for 470 A
Environment18–28 °C (recommended 23 ± 5 °C), below 90 % relative humidity, non-condensing
Storage0–40 °C
CoolingAir cooling
Degree of protectionIP20
CommunicationRS485 and TCP/IP to the UPS system, dry contact, LED status indication
ProtectionBreaker and fuse in the rack, short-circuit fuse and overcharge cut-off in the cells
Module casingFlame-retardant plastic to UL 94 V-0
ExpansionThe rack can be built with 10–17 modules (20.4–34.6 kWh), and several racks can be connected in parallel up to 5 MW

Sources: Samsung SDI product specification for lithium-ion battery system for UPS (34.6 kWh rack, 136S) and the UPS supplier's datasheet and product page for the rack (2026).

Bluecircle

From sizing to operation

We size the battery system according to your emergency preparedness plan, deliver and commission it, and service it afterwards with a fixed response time.