Samsung SDI · Lithium-ion
Samsung SDI UPS rack34.6 kWh lithium-ion battery system
A complete battery rack for UPS systems: 17 modules with Samsung SDI cells, a breaker unit with battery management and a power supply in one cabinet. The rack measures 650 × 530 mm, weighs 510 kg and can be connected in parallel with more racks when the system needs more power or longer backup time.

Design
Breaker, management and 17 modules in one cabinet
At the top is the breaker unit with a moulded case circuit breaker, a shunt for current measurement and the rack BMS. Below it is the power supply, which provides 24 V to the battery management and communicates with the UPS system and any parallel racks.
The modules sit in two columns. Each module has 8 cells in series and its own BMS, and the cables enter at the top of the cabinet.
Battery management
Every cell is monitored, all the way to the UPS system
The module BMS measures voltage and temperature and balances the cells. The rack BMS collects data from all modules and calculates the state of charge (SoC) and state of health (SoH), which the UPS system can read via RS485 or TCP/IP.
Each cell also has a safety vent, a separator that stops overcharging, a short-circuit fuse and an overcharge cut-off.
How we size
The backup time follows your emergency preparedness plan, not the battery's datasheet. We start from how long the UPS system must bridge until the generator has taken over, and build 25 % expansion capacity into the number of racks.
Parallel racks
Several racks side by side
The rack is 650 mm wide and stands side by side with more racks of the same kind. The power supply in each rack communicates with the other racks and with the UPS system, so the system is managed as a whole. According to the supplier, racks can be connected in parallel up to 5 MW.
The rack must stand in a room at 18–28 °C, so we review cooling and placement before we size.

Samsung SDI
Two lithium-ion solutions for UPS systems
Samsung SDI has supplied batteries for data centres since 2017. U8A3-UPS is the new high-power solution for AI data centres, while the 34.6 kWh rack is the established solution for UPS systems today.
| Solution | Cells | Design | Safety | Status |
|---|---|---|---|---|
| SDI U8A3-UPS | LMO, prismatic cells | High power for AI data centres | First UPS solution to meet all criteria in UL Solutions' LSFT | New, CES 2027 |
| UPS rack 34.6 kWh | NMC/LMO, 67 Ah | 17 modules, 516.8 V | BMS at cell, module and rack level | Available today |
Technical data
Samsung SDI UPS rack 34.6 kWh in figures
Data from Samsung SDI's product specification and the UPS supplier's datasheet for the rack.
| Chemistry | Lithium-ion (NMC/LMO), cells of 3.8 V and 67 Ah |
|---|---|
| Design | 1 breaker unit, 1 power supply and 17 battery modules with 8 cells in series each |
| Energy | 34.6 kWh |
| Nominal voltage | 516.8 V DC |
| Float voltage | 571.2 V DC |
| Discharge voltage | Recommended end voltage 435.2 V, cut-off at 408 V |
| Standard charging current | 22.3 A (1/3 C) |
| Discharge current | 470 A for 60 seconds, 600 A for 1 second |
| Dimensions (W × D × H) | 650 × 530 × 2,055 mm |
| Weight | 510 kg with batteries, 17 kg per module |
| Cable connection | 2 conductors, cables enter at the top, cable rated for 470 A |
| Environment | 18–28 °C (recommended 23 ± 5 °C), below 90 % relative humidity, non-condensing |
| Storage | 0–40 °C |
| Cooling | Air cooling |
| Degree of protection | IP20 |
| Communication | RS485 and TCP/IP to the UPS system, dry contact, LED status indication |
| Protection | Breaker and fuse in the rack, short-circuit fuse and overcharge cut-off in the cells |
| Module casing | Flame-retardant plastic to UL 94 V-0 |
| Expansion | The rack can be built with 10–17 modules (20.4–34.6 kWh), and several racks can be connected in parallel up to 5 MW |
Sources: Samsung SDI product specification for lithium-ion battery system for UPS (34.6 kWh rack, 136S) and the UPS supplier's datasheet and product page for the rack (2026).
Bluecircle
From sizing to operation
We size the battery system according to your emergency preparedness plan, deliver and commission it, and service it afterwards with a fixed response time.
Should the Samsung SDI UPS rack 34.6 kWh be sized for your UPS system?
Send us the power of the UPS system, the required backup time and the level of redundancy. We will get back to you with a sizing and a quotation.