ZincFive · High-rate

ZincFive BC 2The standard cabinet in the BC 2 series

BC 2 is ZincFive's standard cabinet with 36–39 nickel-zinc blocks of 80 Ah in a single string. It delivers up to 280 kW per cabinet with more than 5 minutes of backup time and, according to ZincFive, is about half as wide as lithium-ion with the same power.

ZincFive BC 2 battery cabinet
ZincFive's product photo
Up to 280 kWPower per cabinet
Over 5 minBackup time
36–39 kWhEnergy at C/2
10 yearsWarranty at string level

Design

Everything in one cabinet, service from the front

The batteries are delivered installed in the cabinet. The blocks sit on pull-out shelves, the cables enter at the top via a high-voltage box, and all service takes place from the front. The cabinet can therefore stand against a wall or side by side with other cabinets.

The breaker is operated with the door closed and disconnects the batteries from the UPS system, manually or on a fault.

How we size

The backup time follows your emergency preparedness plan, not the battery's datasheet. We start from how long the UPS system must bridge until the generator has taken over, and build 25 % expansion capacity into the number of cabinets.

ZincFive BC 2 seen from the front with high-voltage box, breaker, battery management and pull-out shelves with nickel-zinc blocks High-voltage boxBreaker and BMSPull-out shelves Cables in at the topOperated with door closed36–39 blocks in one string 533 mm 2,121 mm
ZincFive BC 2 seen from the front. Dimensions according to ZincFive's datasheet.

Nickel-zinc

When a block weakens, the string keeps running

In a string of lead-acid batteries, one worn-out block can break the entire string, so the backup is lost exactly when it is needed. A nickel-zinc block that is discharged or weakened still conducts current. The string delivers less, but it does not break.

The battery management system (BMS) monitors voltage, temperature and current on every block and on the whole string. In the event of a fault, the cabinet itself disconnects the batteries from the UPS system.

A weakened block breaks a string of lead-acid batteries, but a string of nickel-zinc blocks still delivers current LEAD-ACID (VRLA) The string is broken NICKEL-ZINC (NIZN) weak block The string still delivers
The principle behind ZincFive's string design: a weakened nickel-zinc block still conducts current.

No thermal runaway

ZincFive's cells have been tested to UL 9540A with no thermal runaway in any of the tests. The electrolyte is water-based potassium hydroxide, not acid.

About half the weight of lead

A cabinet weighs about half as much as lead-acid batteries with the same power. That reduces the floor load in the UPS room.

Tolerates hot periods

The operating range is 20–35 °C. The warranty allows up to 50 °C for no more than 5 % of the operating time, for example if the cooling fails.

Nickel and zinc are recovered

According to ZincFive, all nickel and zinc can be recovered. BC 2 has a cradle-to-grave life cycle assessment from UL Solutions.

BC 2 series

Four models in the same cabinet

All four models sit in a cabinet measuring 533 × 914 mm and 2,096 mm high. The difference lies in the battery blocks, and in how much power and how long a backup time the cabinet is built for. All can be used with megawatt UPS systems, and Vertiv carries the BC series in its own range.

The four cabinets in the ZincFive BC 2 series side by side, with maximum power per cabinet BC 2≤ 280 kWBC 2-300X280–325 kWBC 2-500< 400 kWBC 2 AI280–325 kW
Maximum power per cabinet according to ZincFive's model overview.
ModelBlock capacityPower per cabinetBackup timeMax. discharge currentWeight
BC 280 AhUp to 280 kWOver 5 min800 AUp to 930 kg
BC 2-300X90 Ah280–325 kWOver 5 min800 AUp to 966 kg
BC 2-50090 AhUnder 400 kWUp to 5 min1,200 AUp to 971 kg
BC 2 AI90 Ah280–325 kWOver 5 min800 AUp to 966 kg

Technical data

ZincFive BC 2 in figures

Data from ZincFive's datasheet. Where values depend on the number of blocks in the string, the range is given.

ChemistryNickel-zinc (NiZn), water-based potassium hydroxide electrolyte
Battery blocks36–39 × Z5 13-80 HSF, 80 Ah, in a single string
Nominal voltage468–507 V (36–39 blocks)
Power per cabinetUp to 280 kW
Backup timeOver 5 min, up to 15 min at lower power
Max. discharge current800 A
Charging current20–160 A
Charging time, 0–100 %2–5 hours depending on the charging current
Energy at C/236–39 kWh
Dimensions (W × D × H)533 × 914 × 2,096 mm, 2,121 mm with high-voltage box
Cable entry and serviceCables enter at the top, all service from the front
Environment20–35 °C, up to 50 °C for no more than 5 % of operating time, 0–90 % relative humidity, non-condensing
Storage−20 to 50 °C, no more than 6 months at 25 °C before charging
CoolingForced ventilation with fans
Auxiliary supply100–240 V AC, 50/60 Hz, additional AC or 600 V DC supply as an option
CommunicationEthernet and Modbus TCP/RTU
BreakerOperated with the door closed, disconnects the batteries from the UPS system manually or on a fault
SeismicIBC 2021 and ICC AC156 (SDS 2.29 g)
WeightUp to 930 kg
StandardsIEC 62040-1, IEC 62040-2, CE, UKCA and RoHS, UL 1973 and UL 1778, cells tested to UL 9540A
Warranty10 years at string level at up to 35 °C

Sources: ZincFive BC 2 Series datasheet MKT-LIT-0062 rev. 4.0 (2025), BC 2 AI datasheet rev. 2.0 (2026), ZincFive's model overview and FAQ for the BC series (April 2026), life cycle assessment for BC 2 (UL Solutions, 2026) and Vertiv's product page for BC 2 (warranty).

Bluecircle

From sizing to operation

We size the battery system according to your emergency preparedness plan, deliver and commission it, and service it afterwards with a fixed response time.

Should BC 2 be sized for your UPS system?

Send us the power of the UPS system, the required backup time and the level of redundancy. We will get back to you with a sizing and a quotation.

+45 7012 1317kontakt@blue-circle.dkGet a quotation