ZincFive · High-rate

ZincFive BC 2-300XLonger backup time in the same cabinet

BC 2-300X has the same 90 Ah blocks as BC 2-500 but is built for backup times over 5 minutes. The cabinet delivers 280–325 kW and suits systems where the emergency preparedness plan requires more time than an ultra-high-rate cabinet provides.

ZincFive BC 2-300X battery cabinet
ZincFive's product photo
280–325 kWPower per cabinet
Over 5 minBackup time
90 AhNickel-zinc blocks
800 AMax. discharge current

Power and time

More energy than BC 2 in the same cabinet

With 90 Ah instead of 80 Ah per block, BC 2-300X holds more energy in the same cabinet as BC 2. It can be used for more power at the same backup time or for longer backup time at the same power.

According to ZincFive, BC 2-300X takes up to 50 % less space than other battery solutions with the same power.

How we size

The backup time follows your emergency preparedness plan, not the battery's datasheet. We start from how long the UPS system must bridge until the generator has taken over, and build 25 % expansion capacity into the number of cabinets.

Power per cabinet and backup time for the four models in the BC 2 series BC 2≤ 280 kWOver 5 min backup timeBC 2-300X280–325 kWOver 5 min backup timeBC 2-500< 400 kWUp to 5 min backup timeBC 2 AI280–325 kWOver 5 min backup time and AI pulses
Maximum power per cabinet and backup time according to ZincFive's model overview.

Nickel-zinc

When a block weakens, the string keeps running

In a string of lead-acid batteries, one worn-out block can break the entire string, so the backup is lost exactly when it is needed. A nickel-zinc block that is discharged or weakened still conducts current. The string delivers less, but it does not break.

The battery management system (BMS) monitors voltage, temperature and current on every block and on the whole string. In the event of a fault, the cabinet itself disconnects the batteries from the UPS system.

A weakened block breaks a string of lead-acid batteries, but a string of nickel-zinc blocks still delivers current LEAD-ACID (VRLA) The string is broken NICKEL-ZINC (NIZN) weak block The string still delivers
The principle behind ZincFive's string design: a weakened nickel-zinc block still conducts current.

No thermal runaway

ZincFive's cells have been tested to UL 9540A with no thermal runaway in any of the tests. The electrolyte is water-based potassium hydroxide, not acid.

About half the weight of lead

A cabinet weighs about half as much as lead-acid batteries with the same power. That reduces the floor load in the UPS room.

Tolerates hot periods

The operating range is 20–35 °C. The warranty allows up to 50 °C for no more than 5 % of the operating time, for example if the cooling fails.

Nickel and zinc are recovered

According to ZincFive, all nickel and zinc can be recovered. BC 2 has a cradle-to-grave life cycle assessment from UL Solutions.

BC 2 series

Four models in the same cabinet

All four models sit in a cabinet measuring 533 × 914 mm and 2,096 mm high. The difference lies in the battery blocks, and in how much power and how long a backup time the cabinet is built for. All can be used with megawatt UPS systems, and Vertiv carries the BC series in its own range.

The four cabinets in the ZincFive BC 2 series side by side, with maximum power per cabinet BC 2≤ 280 kWBC 2-300X280–325 kWBC 2-500< 400 kWBC 2 AI280–325 kW
Maximum power per cabinet according to ZincFive's model overview.
ModelBlock capacityPower per cabinetBackup timeMax. discharge currentWeight
BC 280 AhUp to 280 kWOver 5 min800 AUp to 930 kg
BC 2-300X90 Ah280–325 kWOver 5 min800 AUp to 966 kg
BC 2-50090 AhUnder 400 kWUp to 5 min1,200 AUp to 971 kg
BC 2 AI90 Ah280–325 kWOver 5 min800 AUp to 966 kg

Technical data

ZincFive BC 2-300X in figures

Data from ZincFive's datasheet. Where values depend on the number of blocks in the string, the range is given.

ChemistryNickel-zinc (NiZn), water-based potassium hydroxide electrolyte
Battery blocks36–39 × Z5 13-90 USF, 90 Ah, in a single string
Nominal voltage468–507 V (36–39 blocks)
Power per cabinet280–325 kW
Backup timeOver 5 min, up to 15 min at lower power
Max. discharge current800 A
Charging current20–160 A
Charging time, 0–100 %2–5 hours depending on the charging current
Dimensions (W × D × H)533 × 914 × 2,096 mm, 2,121 mm with high-voltage box
Cable entry and serviceCables enter at the top, all service from the front
Environment20–35 °C, up to 50 °C for no more than 5 % of operating time, 0–90 % relative humidity, non-condensing
Storage−20 to 50 °C, no more than 6 months at 25 °C before charging
CoolingForced ventilation with fans
Auxiliary supply100–240 V AC, 50/60 Hz, additional AC or 600 V DC supply as an option
CommunicationEthernet and Modbus TCP/RTU
BreakerOperated with the door closed, disconnects the batteries from the UPS system manually or on a fault
SeismicIBC 2021 and ICC AC156 (SDS 2.29 g)
WeightUp to 966 kg
StandardsIEC 62040-1, IEC 62040-2, CE, UKCA and RoHS, UL 1973 and UL 1778, cells tested to UL 9540A
Warranty10 years at string level at up to 35 °C

Sources: ZincFive BC 2 Series datasheet MKT-LIT-0062 rev. 4.0 (2025), BC 2 AI datasheet rev. 2.0 (2026), ZincFive's model overview and FAQ for the BC series (April 2026), life cycle assessment for BC 2 (UL Solutions, 2026) and Vertiv's product page for BC 2 (warranty).

Bluecircle

From sizing to operation

We size the battery system according to your emergency preparedness plan, deliver and commission it, and service it afterwards with a fixed response time.

Should BC 2-300X be sized for your UPS system?

Send us the power of the UPS system, the required backup time and the level of redundancy. We will get back to you with a sizing and a quotation.

+45 7012 1317kontakt@blue-circle.dkGet a quotation